B.I.E. REVIEW (FIRE HYDRANT EQUIPPED):

According to current regulations (R.D 513/2017), it will carry out the review at least once a year (Table II), this review is to:
Removing the hose and test it in place.
Checking the correct operation of the nozzle in different positions, and locking system.
Leak testing of the fittings, hose, and state boards.
Check the gauge reading with another reference (standard) coupled to the fitting connecting the hose.

STAMPING HOSE:

Denomination is called the "pressure test" to be submitted to both major vessels as well as hoses that are fitted with some extinguishing systems.

The retimbrado or "pressure test" must be done every 5 years from the date of manufacture and record the date of the transaction approval in the hose or in the same container.

Be provided by FLAMASUR, SL the corresponding Certificate of fire extinguishers have been subjected to such tests.